Instructions: back to home page
- Print
these pages.
- Circle
the correct answers.
- Page
down to the last page for the verification forms and mailing instructions.
05 changes-1
5 Hours of Credit
Article 90 Introduction
Utilities may be subject to
compliance with codes and standards covering their regulated activities as
adopted under governmental law or regulation.
(a) True
(b) False
Chapter 1
General
Article 100 Definitions
- The localization of an
overcurrent condition to restrict outages to the circuit or equipment
affected, accomplished by the choice of overcurrent-protective devices is
called _____.
(a) overcurrent protection
(b) interrupting capacity
(c) selective coordination
(d) overload protection
A _____ is a
single unit that provides independent living facilities for persons, including
permanent provisions for living, sleeping, cooking, and sanitation.
(a)
two-family dwelling
(b)
one-family dwelling
(c) dwelling
unit
(d) multifamily
dwelling
- The grounding electrode
conductor is the conductor used to connect the grounding electrode to the
equipment grounding (bonding) conductor and the grounded neutral conductor
at _____.
(a) the service
(b) each building or structure
supplied by feeder(s)
(c) the source of a separately
derived system
(d) all of these
A _____ is an
accommodation with two or more contiguous rooms comprising a compartment, with
or without doors between such rooms that provides living, sleeping, sanitary and storage facilities.
(a) guest room
(b) guest suite
(c) dwelling unit
(d) single family dwelling
- A(n) _____ system is a premises
wiring system whose power is derived from a source of electric energy or
equipment other than a service, and that has no direct electrical connection,
including a solidly connected grounded circuit conductor, to supply
conductors originating in another system.
(a) separately derived
(b) classified
(c) direct
(d) emergency
Article 110 Requirements for Electrical
Installations
- Accepted industry workmanship
practices are described in ANSI/NECA 1-2000, Standard Practices for
Good Workmanship in Electrical Contracting, and other ANSI approved
installation standards.
(a) True
(b) False
- For equipment rated 1,200A or
more that contains overcurrent devices, switching devices, or control
devices at least one entrance, measuring not less than 24 in. wide and 6
ft, 6 in. high, must be provided at each end of the working space. Where
the entrance to the working space has a personnel door, the door _____.
(a) must open either in or out with
simple pressure and shall not have any lock
(b) must open in the direction of
egress and be equipped with panic hardware or other devices so the door can
open under simple pressure
(c) must be removed
(d) must be equipped with an
electronic opener
Chapter 2
Wiring and Protection
Article 200 Use and Identification of
grounded neutral conductors
- Grounded
neutral conductors larger than 6 AWG must be identified by _____.
(a) a
continuous white or gray outer finish along their entire length
(b) three
continuous white stripes along their entire length
(c) distinctive white or gray
tape or paint at terminations
(d) a, b,
or c
- The white
conductor within a cable can be used for the ungrounded (hot) conductor,
but the white conductor must be permanently reidentified
to indicate its use as an ungrounded (hot) conductor at each location
where the conductor is visible and accessible. Identification must _____.
(a) be by painting or other
effective means
(b) be a color other than white,
gray, or green
(c) both a and b
(d) none of these
Article 210 Branch Circuits
- Where more than one nominal
voltage system exists in a building, each _____ conductor of a branch circuit,
where accessible, shall be identified by system.
(a) grounded
(b) ungrounded
(c) grounding
(d) all of these
GFCI protection is required for all 15 and 20A, 125V
single-phase receptacles located within an arc
measurement of 6 ft from the dwelling unit _____.
(a) laundry sink
(b) utility sink
(c) wet bar sink
(d) all of these
- In other than dwelling units,
GFCI protection is required _____.
(a) for outdoor 15 and
20A, 125V single-phase receptacles accessible to the public
(b) at an accessible location for
HVAC equipment
(c) both a and b
(d) neither a or b
- A receptacle outlet must be
installed at each wall counter space that is 12 in. or wider so that no
point along the wall line is more than _____, measured horizontally, from
a receptacle outlet in that space.
(a) 10 in.
(b) 12 in.
(c) 16 in.
(d) 24 in.
- One
receptacle outlet must be installed at each island or peninsular
countertop space with a long dimension of 2 ft or greater, and a short
dimension of 12 in. or greater. When breaks occur in countertop spaces for
appliances, sinks, etc., there is never a need for more than one total
receptacle outlet.
(a) True
(b) False
- In dwelling units, at
least one wall receptacle outlet must be installed in bathrooms within
_____ of the outside edge of each basin. The receptacle outlet must be
located on a wall or partition that is adjacent to the basin or basin
countertop.
(a) 12 in.
(b) 18 in.
(c) 24 in.
(d) 36 in.
- Guest rooms in hotels, motels,
and similar occupancies without permanent provisions for cooking must have
receptacle outlets installed in accordance with 210.52(A) and 210.52(D).
(a) True
(b) False
- A 15 or 20A, 125V, single-phase
receptacle outlet must be installed at an accessible location for the servicing
of heating, air-conditioning, and refrigeration equipment. The receptacle
must be located on the same level and within _____ of the heating,
air-conditioning, and refrigeration equipment.
(a) 10 ft
(b) 15 ft
(c) 20 ft
(d) 25 ft
Article 215 Feeders
- The size of the grounded
neutral conductor for a feeder must not be smaller than specified in
_____.
(a) Table 250.122
(b) Table 250.66
(c) Table 310.16
(d) Table 430.52
Article 225 Outside
Branch Circuits and Feeders
- Raceways on
exterior surfaces of buildings or other structures must be arranged to
drain, and in _____ locations must be raintight.
(a) damp
(b) wet
(c) dry
(d) all of
these
Article 230 Services
- Additional services are permitted
for different voltages, frequencies, or phases, or for different uses such
as for _____.
(a) gymnasiums
(b) different rate schedules
(c) flea markets
(d) special entertainment events
- The additional service
disconnecting means for fire pumps or for emergency, legally required
standby, or optional standby services permitted by 230.2, must be
installed remote from the one to six service disconnecting means for
normal service to minimize the possibility of _____ interruption of
supply.
(a) accidental
(b) intermittent
(c) simultaneous
(d) prolonged
Article 240 Overcurrent Protection
- Single-pole breakers with
identified handle ties can be used to protect each ungrounded conductor
for line-to-line connected loads.
(a) True
(b) False
- The “next size
up protection rule“ of 240.4(B) is permitted for
transformer secondary tap conductors.
(a) True
(b) False
- Overcurrent protection devices
must be _____.
(a) accessible (as applied to
wiring methods)
(b) accessible (as applied to
equipment)
(c) readily accessible
(d) inaccessible to unauthorized
personnel
Article 250 Grounding and Bonding
- An effective ground-fault
current path is created when all electrically conductive materials that
are likely to be energized are bonded together and to the _____.
(a) ground
(b) earth
(c) electrical supply source
(d) none of these
- The grounding electrode
conductor at the service is permitted to terminate on an
equipment grounding terminal bar if a (main) bonding jumper is
installed between the grounded neutral conductor bus and the equipment
grounding terminal.
(a) True
(b) False
- A grounding electrode is
required if a building or structure is supplied by a feeder or by more
than one branch circuit.
(a) True
(b) False
- The frame of a vehicle-mounted generator
is not required to be connected to a _____ for a system supplied by cord
and plug using receptacles mounted on the vehicle or the generator when
the grounding terminals of the receptacles are bonded to the generator
frame and the generator frame is bonded to the vehicle frame.
(a) grounding electrode
(b) grounded neutral conductor
(c) ungrounded conductor
(d) equipment grounding (bonding)
conductor
- Interior metal water piping
located more than _____ from the point of entrance to the building cannot
be used as a part of the grounding electrode system, or as a conductor to
interconnect electrodes that are part of the grounding electrode system.
(a) 2 ft
(b) 4 ft
(c) 5 ft
(d) 6 ft
- For electrical equipment
supplementary electrodes:
(1) A bond to the grounding electrode system is not
required.
(2) The bonding jumper to the supplementary electrode can be
any size.
(3) The 25 ohm resistance requirement of 250.56 does not
apply.
(a) True
(b) False
- Metal enclosures for grounding electrode
conductors must be electrically continuous from the point of attachment to
cabinets or equipment to the grounding electrode.
(a) True
(b) False
- Service equipment, service
raceways, and service conductor enclosures must be bonded _____.
(a) to the grounded service
conductor
(b) by threaded raceways into
enclosures, couplings, hubs, conduit bodies, etc.
(c) by listed bonding devices with
bonding jumpers
(d) any of these
- Exposed structural steel that
is interconnected to form a steel building frame, is not intentionally
grounded and is likely to become energized, must be bonded to:
(a) The service equipment enclosure.
(b) The grounded neutral conductor at the service.
(c) The grounding electrode conductor where of sufficient
size.
(d) any of these
- For
flexible metal conduit (FMC) and liquidtight
flexible metal conduit (LFMC), an equipment
grounding (bonding) conductor is required regardless of the size of the
overcurrent protection if the FMC or LFMC is installed for the reason of
_____.
(a) physical
protection
(b) flexibility
(c) protection
from moisture
(d) communication
systems
- An equipment grounding (bonding) conductor
must be identified by _____.
(a) a continuous outer finish that
is green
(b) being bare
(c) a continuous outer finish that
is green with one or more yellow stripes
(d) any of these
- Where a metal box is
surface-mounted, direct metal-to-metal contact between the device yoke and
the box is permitted to ground the receptacle to the box. Unless the
receptacle is listed as _____, at least one of the insulating retaining
washers must be removed from the receptacles to ensure direct
metal-to-metal contact between the device yoke and metal outlet box.
(a) self-grounding
(b) weatherproof
(c) metal contact sufficient
(d) isolated grounding
- An equipment bonding jumper for
a grounding-type receptacle must be installed between the receptacle and a
flush-mounted outlet box, even when the contact device is listed as
self-grounding.
(a) True
(b) False
Chapter 3
Wiring Methods and Materials
Article 300 Wiring Methods
- When unable to maintain the
minimum required distance from the edge of a wood framing member to a
bored hole for cable or nonmetallic raceway installation, the cable or
raceway must be protected from penetration by screws or nails by a steel
plate or bushing at least _____ and of appropriate length and width to
cover the area of the wiring. A thinner plate that provides equal or
better protection may be used if listed and marked.
(a) ¼ inch thick
(b) 1/8 inch thick
(c) 1/16 inch thick
(d) 24 gauge
- In both exposed and concealed
locations, where a cable or nonmetallic raceway-type wiring method is
installed parallel to framing members such as joists, rafters, or studs or
furring strips, the nearest outside surface of the cable or raceway must
be _____ the nearest edge of the framing member where nails or screws are
likely to penetrate.
(a) not less than 1¼ inch from
(b) immediately adjacent to
(c) not less than 1/16 inch from
(d) 90°away from
- Nonferrous raceways, cable
trays, cablebus, auxiliary gutters, cable armor,
boxes, cable sheathing, cabinets, elbows, couplings, nipples, fittings,
supports and support hardware _____ must be provided with supplementary
corrosion protection.
(a) embedded or encased in concrete
(b) in direct contact with the
earth
(c) likely to become energized
(d) a or b
- Nonmetallic raceways, cable
trays, cablebus, auxiliary gutters, boxes, and
cables with a nonmetallic outer jacket must be made of material approved
for the condition and where exposed to chemicals, the materials or
coatings must be _____.
(a) listed as inherently resistant
to chemicals
(b) identified for the specific
chemical reagent
(c) both a and b
(d) either a or b
- Short sections of raceways used
for _____ are not required to be installed complete between outlet,
junction, or splicing points.
(a) meter to service enclosure
connection
(b) protection of cables from
physical damage
(c) nipples
(d) separately derived systems
Article 310 Conductors
- Conductors
installed in conduit exposed to direct sunlight in close proximity to
rooftops have been shown, under certain conditions, to experience an
increase in temperature of _____°F above ambient temperature.
(a) 70
(b) 10
(c) 30
(d) 40
- For individual dwelling units
of _____ dwellings, Table 310.15(B)(6) can be used to size 3-wire, 1Ø,
120/240V service or feeder conductors that serve as the main
power feeder to a dwelling unit.
(a)
one-family
(b) two-family
(c) multifamily
(d) any of
these
Article 314 Outlet, Device, Pull and
Junction Boxes, Conduit Bodies, Fittings and Handhole Enclosures
- When counting the number of
conductors in a box, a conductor running through the box with no loop in
it is counted as _____ conductor(s).
(a) one
(b) two
(c) zero
(d) none of these
- In walls or ceilings
constructed of wood or other combustible surface material, boxes, plaster
rings, extension rings, or listed extenders must _____.
(a) be flush with the surface
(b) project from the surface
(c) a or b
(d) be set back no more than ¼ in.
- Where a box is used as the sole
support of a ceiling-suspended (paddle) fan, the box must be listed for
the application and must be marked with the weight of the fan to be
supported if over 35 lbs.
(a) True
(b) False
- Handhole enclosures must
be sized in
accordance with 314.28(A) for conductors operating at 600 volts and below.
For handhole enclosures without bottoms, the measurement to the removable
cover is taken from the _____.
(a) end of the conduit or cable
assembly
(b) lowest point in the hole
(c) leveling marks provided
(d) highest possible ground water
level.
- Handhole enclosure covers must
have an
identifying _____ that prominently identifies the function of the
enclosure, such as “electric.”
(a) mark
(b) logo
(c) a or b
(d) manual
To obtain your Continuing
Education Credits follow the below instructions.
- Print
out first.
- The
state allows a person to take the same course more than once (several
times) per cycle.
- If taking
the same quiz more than once per cycle, fill out the forms with different
dates.
- Fill
in all fields applicable.
- Include
your certification or license number.
- We’ll
take care of crediting with the state and mailing back to you the quiz
results.
Send by mail
- Test
& answer sheets.
- Fill
out this form below completely.
- Applicable
fees by check payable to Gary Klinka.
- Mail to: Gary Klinka at 228 Mandella Ct Neenah
WI 54956.
- Questions call: 920-727-9200 office and fax or
920-740-6723 cell garyklinka@hotmail.com
----------------------------Educational Course
Attendance Verification Form ------------------------
Attendee’s Name
Date
Address
Credential Number
Phone#
Course Title and Name 05
changes
1
List the name of each credential held by attendee