Page
down to the last page for the verification forms and mailing instructions.
05 changes-3
5 Hours of Credit
Chapter 1
General
Article 100 Definitions
The connection between the
grounded circuit conductor and the equipment grounding (bonding) conductor
at a separately derived system is the _____.
(a) main bonding jumper
(b) system bonding jumper
(c) circuit bonding jumper
(d) equipment bonding jumper
Which of the following does the
Code recognize as a device?
(a) Switch
(b) Light bulb
(c) Transformer
(d) Motor
A device that establishes an
electrical connection to the earth is the _____.
(a) grounding electrode conductor
(b) grounding conductor
(c) grounding electrode
(d) grounded neutral conductor
A _____ is an accommodation
that combines living, sleeping, sanitary, and storage facilities.
(a) guest room
(b) guest suite
(c) dwelling unit
(d) single family dwelling
Outline
lighting may include an arrangement of _____to outline or call
attention to certain features such as the shape of a building or the
decoration of a window.
(a) incandescent
lamps
(b) electric-discharge lighting
(c) electrically
powered light sources
(d) a, b,
or c
NFPA 70E, Electrical Safety
Requirements for Employee Workplaces provides information to help
determine the electrical safety training requirements expected of a
“qualified person.”
(a) True
(b) False
Article 110 Requirements for Electrical
Installations
The NEC requires that
electrical work be installed _____.
(a) in a neat and workmanlike
manner
(b) under the supervision of a
qualified person
(c) completed before being
inspected
(d) all of these
Enclosures housing electrical
apparatus that are controlled by a lock are be considered _____ to
qualified persons.
(a) readily accessible
(b) accessible
(c) available
(d) none of these
Chapter 2
Wiring and Protection
Article 200 Use and Identification of
Grounded Neutral Conductors
Grounded neutral conductors
_____ and larger shall be identified by a continuous white or gray outer
finish along their entire lengths, by three continuous white stripes along
their entire length, or by distinctive white or gray markings such as
tape, paint or other effective means at their terminations.
(a) 10 AWG
(b) 8 AWG
(c) 6 AWG
(d) 4 AWG
Where
grounded neutral conductors of different wiring systems are installed in
the same raceway, cable, or enclosure, each grounded neutral conductor
must be identified in a manner that makes it possible to distinguish the
grounded neutral conductors for each system. This means of identification
must be_____.
(a) permanently
posted at each branch-circuit panelboard
(b) posted
inside each junction box where both system neutrals are present
(c) done
using a listed labeling technique
(d) all of
these
Article 210 Branch Circuits
Where more than one nominal
voltage system exists in a building, each ungrounded conductor of a branch
circuit, where accessible, must be identified by system. The
identification can be _____ and shall be permanently posted at each
branch-circuit panelboard.
(a) color-coding
(b) phase tape
(c) tagging
(d) any of these
Where two or more
branch circuits supply devices or equipment on the same yoke, a means to
disconnect simultaneously all ungrounded (hot) conductors that supply those devices or
equipment must be provided _____.
(a) at the point where the branch
circuit originates
(b) at the location of the device
or equipment
(c) at the point where the feeder
originates
(d) none of these
In locations other than
dwelling units, a kitchen _____.
(a) is required to have GFCI
protection on all 15 and 20A, 125V single-phase receptacles
(b) includes a sink
(c) includes permanent facilities
for food preparation and cooking
(d) all of these
All branch circuits that supply
15 and 20A, 125V single-phase outlets installed in dwelling unit bedrooms
must be protected by a(n) _____ listed to provide
protection of the entire branch circuit.
(a) AFCI
(b) GFCI
(c) a and b
(d) none of these
_____ provided with
permanent provisions for cooking must have branch circuits and outlets
installed to meet the rules for dwelling units.
(a) Guest rooms
(b) Guest suites
(c) Commercial kitchens
(d) a and b
At least one receptacle outlet
must be installed at each peninsular countertop or island not containing a
sink or range top, having a long dimension of _____ in. or greater, and a
short dimension of _____ in. or greater.
(a) 12, 24
(b) 24, 12
(c) 24, 48
(d) 48, 24
When breaks occur in dwelling
unit kitchen-countertop spaces for ranges, refrigerators, sinks, etc.,
each countertop surface is considered a separate counter space for
determining receptacle placement.
(a) True
(b) False
At least one receptacle outlet
accessible from grade level and not more than _____ above grade must be
installed at each dwelling unit of a multifamily dwelling located at grade
level and provided with individual exterior entrance/egress.
(a) 3 ft
(b) 6½ ft
(c) 8 ft
(d) 24 in.
The number
of receptacle outlets for guest rooms in hotels and motels must not be
less than that required for a dwelling unit, in accordance with 210.52(A).
These receptacles can be located to be convenient for permanent furniture
layout, but not less than _____ receptacle outlets must be readily
accessible
(a) 4
(b) 2
(c) 6
(d) 1
At least
one wall switch-controlled lighting outlet must be installed in every habitable room and
bathroom of a guest room or guest suite of hotels, motels, and
similar occupancies. A receptacle outlet controlled by a wall switch may
be used to meet this requirement in other than _____.
(a) bathrooms
(b) kitchens
(c) sleeping
areas
(d) both a
and b
Article 215 Feeders
Article 225 Outside
Branch Circuits and Feeders
Where a
mast is used for overhead conductor support of outside branch circuits and
feeders, it must have adequate mechanical strength, or braces or guy wires
to support it, to withstand the strain caused by the conductors. Only
_____ conductors can be attached to the mast.
(a) communications
(b) fiber
optic
(c) feeder
or branch circuit
(d) all of these
More than one feeder or branch
circuit is permitted to supply a single building or other structure
sufficiently large to require two or more supplies if permitted by _____.
(a) architects
(b) special permission
(c) written authorization
(d) master electricians
Article 230 Services
Disconnecting means used solely
for power monitoring equipment, transient voltage surge suppressors, or
the control circuit of the ground-fault protection system or
power-operable service disconnecting means, installed as part of the
listed equipment, are not considered a service disconnecting means.
(a) True
(b) False
Article 240 Overcurrent Protection
Where flexible cord is used in
listed extension cord sets, the conductors are
considered protected against overcurrent when used within _____.
(a) indoor installations
(b) non-hazardous locations
(c) the extension cord’s listing
requirements
(d) 50 ft of the branch-circuit panelboard
One of the requirements that
permit conductors supplying a transformer to be tapped, without overcurrent
protection at the tap, is that the conductors supplied by the _____ of a
transformer must have an ampacity, when multiplied by the ratio of the
primary-to-secondary voltage, of at least one-third of the rating of the
overcurrent device protecting the feeder conductors.
(a) primary
(b) secondary
(c) tertiary
(d) none of these
Circuit
breakers and fuses must be readily accessible and they must be installed
so the center of the grip of the operating handle of the fuse switch or
circuit breaker, when in its highest position, isn’t more than_____ above
the floor or working platform.
(a) 6 ft 7 in.
(b) 2 ft
(c) 5 ft
(d) 4 ft 6 in.
Article 250 Grounding and Bonding
An effective ground-fault
current path is an intentionally constructed low-impedance path designed
and intended to carry fault current from the point of a line-to-case fault
on a wiring system to _____.
(a) ground
(b) earth
(c) electrical supply source
(d) none of these
For grounded systems,
electrical equipment and wiring and other electrically conductive material
likely to become energized must be installed in a manner that creates a
_____ from any point on the wiring system where a ground fault may occur
to the electrical supply source.
(a) permanent path
(b) low-impedance path
(c) path capable of safely carrying
the ground-fault current likely to be imposed on it
(d) all of these
Sheet-metal
screws can
be used to connect grounding (or bonding) conductors or connection devices to
enclosures.
(a) True
(b) False
Grounding electrode taps from a
separately derived system to a common grounding electrode conductor are
permitted when a building or structure has multiple separately derived
systems.
(a) True
(b) False
The frame of a portable
generator is not required to be grounded and is not to be connected to a
_____ for a system supplied by cord and plug using receptacles mounted on
the generator with the grounding terminals of the receptacles bonded to
the generator frame.
(a) grounding electrode
(b) grounded neutral conductor
(c) ungrounded conductor
(d) equipment grounding (bonding)
conductor
Concrete-encased
electrodes of _____ are not required to be part of the grounding electrode
system where the steel reinforcing bars or rods aren’t accessible for use without
disturbing the concrete.
(a) hazardous
locations
(b) health
care facilities
(c) existing
buildings or structures
(d) agricultural
buildings with equipotential planes
Grounding electrodes consisting
of stainless-steel rods or nonferrous rods that are less than 5/8 inch in
diameter must be listed and cannot be less than _____ in diameter.
(a) 1/2 in.
(b) 3/4 in.
(c) 1 in.
(d) 11/4
The connection (attachment) of
the grounding electrode conductor to a grounding electrode must _____.
(a) be accessible
(b) be made in a manner that will
ensure a permanent and effective grounding path
(c) a and b
(d) none of these
Metal gas piping can be
considered bonded by the circuit’s equipment grounding (bonding) conductor
of the circuit that is likely to energize the piping.
(a) True
(b) False
Flexible metal conduit can be
used as the equipment grounding (bonding) conductor if the length in any
ground return path does not exceed 6 ft and the circuit conductors
contained in the conduit are protected by overcurrent devices rated at
_____ or less.
(a) 15A
(b) 20A
(c) 30A
(d) 60A
Liquidtight flexible metal
conduit (LFMC) in ¾ through 1¼ inch trade sizes can be used as the
equipment grounding (bonding) conductor if the length in any ground return
path does not exceed 6 ft and the circuit conductors contained in the
conduit are protected by overcurrent devices rated at _____ or less when
the conduit is not installed for flexibility.
(a) 15A
(b) 20A
(c) 30A
(d) 60A
Equipment grounding (bonding)
conductors for feeder taps must be sized in
accordance with _____ based on the ampere rating of the circuit protection
device
ahead of the feeder, but in no case is it required to be larger than
the circuit conductors.
(a) Table 250.66
(b) Table 250.94
(c) Table 250.122
(d) Table 220.19
Receptacle yokes designed and _____ as
self-grounding are permitted to establish the bonding path between
the device yoke and a grounded outlet box.
(a) approved
(b) advertised
(c) listed
(d) installed
Equipment bonding jumpers are
not required for receptacles listed as self-grounding that have mounting
screws to provide the grounding continuity between the metal yoke and the
flush box.
(a) True
(b) False
Chapter 3
Wiring Methods and Materials
Article 300 Wiring Methods
Where nails or screws are
likely to penetrate nonmetallic-sheathed cable or electrical nonmetallic
tubing installed through metal framing members, a steel sleeve, steel
plate or steel clip not less than _____ in thickness must be used to
protect the cable or tubing. A thinner plate that provides equal or better
protection may be used if listed and marked.
(a) 1/16 in.
(b) 1/8 in.
(c) 1/2 in.
(d) none of these
Cable or nonmetallic
raceway-type wiring methods installed in a groove, to be covered by
wallboard, siding, paneling, carpeting or similar finish must be protected
by 1/16 inch thick _____ or by not less than 1¼ in. of free space for the
full length of the groove. A thinner plate that provides equal or better
protection may be used if listed and marked.
(a) steel plate
(b) steel sleeve
(c) PVC bushing
(d) a or b
Nonmetallic raceways, cable
trays, cablebus, auxiliary gutters, boxes, and
cables with a nonmetallic outer jacket must be made of material approved
for the condition and where exposed to sunlight, the materials must be
_____.
(a) listed as sunlight resistant
(b) identified as sunlight
resistant
(c) both a and b
(d) either a or b
Article 310 Conductors
Insulated conductors and cables
exposed to the direct rays of the sun must be _____.
(a) covered with insulating
material that is listed or listed and marked sunlight resistant
(b) listed and marked sunlight
resistant
(c) listed for sunlight resistance
(d) a or b or c
Service and feeder conductors
may be sized using Table 310.15(B)(6) for_____.
(a) any kind of service under 400
amps
(b) only multifamily dwelling
services
(c) only 120/240 volt, 3-wire, 1Ø
services for individual dwelling units
(d) commercial services only
Article 312 Cabinets, Cutout Boxes, and
Meter Socket Enclosures
Plaster,
drywall, or plasterboard surfaces that are broken or incomplete shall be
repaired so there will be no gaps or open spaces greater than _____ at the
edge of a cabinet
or cutout box employing a flush-type cover.
(a) ¼ in
(b) ½ in
(c) 1/8 in
(d) 1/16 in
Article 314 Outlet, Device, Pull and
Junction Boxes, Conduit Bodies, Fittings and Handhole Enclosures
In noncombustible walls or ceilings,
the front edge of a box, plaster ring, extension ring, or listed extender
may be set back not more than _____ from the finished surface.
(a) 3/8 in.
(b) 1/8 in.
(c) 1/2 in.
(d) 1/4 in.
Nails or
screws can fasten boxes to structural members of a building using brackets
on the outside of the enclosure, or they can pass through the interior
within _____ of the back or ends of the enclosure. Screws are not
permitted to pass through the box unless exposed threads in the box are
protected using approved means to avoid abrasions of conductor insulation.
(a) 1/8 in
(b) 1/16 in
(c) ¼ in
(d) ½ in
Handhole enclosures must
be designed
and installed to withstand _____.
(a) 3,000 lb
(b) 6,000 lb
(c) all loads likely to be imposed
(d) 600 lb
Where handhole enclosures
without bottoms are installed, all enclosed conductors and any splices or
terminations, if present, must be listed as _____.
(a) suitable for wet locations
(b) suitable for damp locations
(c) handhole ready
(d) general duty.
To
obtain your Continuing Education Credits follow the below instructions.
Print
out first.
Fill
in all fields applicable.
Include
your certification or license number.
We’ll
take care of crediting with the state and mailing back to you the quiz
results.
Send by mail
Test
& answer sheets.
Fill
out this form below completely.
Applicable
fees by check payable to Gary Klinka.
Mail to: Gary Klinka at 228 Mandella CtNeenahWI54956.