Instructions: back to home page
- Print
these pages.
- Circle
the correct answers.
- Page
down to the last page for the verification forms and mailing instructions.
05 changes-4
5 Hours of Credit
Article 320 Armored Cable: Type AC
- When Type AC cable is installed
in thermal insulation, it must have conductors that are rated at 90°C. The
ampacity of the cable in this application is _____.
(a) based on 90°C column
(b) as labeled by the manufacturer
(c) based on the 60°C column
(d) none of these
Article 330 Metal-Clad Cable: Type MC
- Type MC cable
containing four or fewer conductors, sized no larger than 10 AWG, must be
secured within _____ of every box, cabinet,
fitting, or other cable termination.
(a) 8 in.
(b) 18 in.
(c) 12 in.
(d) 24 in.
Article 334 Nonmetallic-Sheathed Cable:
Types NM, NMC and NMS
- Sections of Type NM
cable protected from physical damage by raceway are not required to be
_____ within the raceway.
(a) covered
(b) insulated
(c) secured
(d) unspliced
Article 348 Flexible Metal Conduit: Type FMC
- FMC must be supported and
secured _____
(a) at intervals not exceeding 41/2
ft
(b) within 8 in. on each side of a
box where fished
(c) where fished
(d) at intervals not exceeding 6 ft
at motor terminals
- When flexible metal conduit is
used to install equipment where flexibility is required, _____ must be
installed.
(a) an equipment grounding
(bonding) conductor
(b) an expansion fitting
(c) flexible nonmetallic connectors
(d) a neutral conductor one size
larger
Article 350 Liquidtight Flexible Metal
Conduit: Type LFMC
- When LFMC is used to connect
equipment requiring flexibility, a separate _____ conductor must be
installed.
(a) main bonding jumper
(b) grounded
(c) equipment grounding
(d) none of these
Article 376 Metal Wireways
- Where insulated conductors are
deflected within a metallic wireway, the wireway must be sized to meet the bending requirements
corresponding to one wire per terminal in Table 312.6(A).
(a) True
(b) False
- Power distribution blocks
installed in metal wireways must _____.
(a) allow for sufficient
wire-bending space at terminals
(b) not have exposed live parts
after installation
(c) either a or b
(d) both a and b
Article 386 Surface Metal Raceways
- Where combination surface metal
raceways are used for both signaling and for lighting and power circuits,
the different systems must be run in separate compartments identified by
_____ of the interior finish.
(a) stamping
(b) imprinting
(c) color-coding
(d) any of these
Chapter 4 Equipment
for General Use
Article 400 Flexible Cords and Cables
- Where flexible cords are used
in ambient temperatures exceeding _____ the temperature correction factors
from Table 310.16 that correspond to the temperature rating of the cord
must be applied to the ampacity from Table 400.5(A) or 400.5(B).
(a) 60°C
(b) 30°C
(c) 75°C
(d) 90°C
Article 404 Switches
- A snap switch without a
grounding connection is allowed for replacement purposes only where the
wiring method does not include an equipment ground and must be _____.
(a) provided with a faceplate of nonconducting, noncombustible material
(b) protected by a ground-fault
circuit interrupter
(c) a or b
(d) none of these
Article 406 Receptacles, Cord Connectors,
and Attachment Plugs (Caps)
- _____, 125 and 250V receptacles
installed in a wet location must have an enclosure that is weatherproof
whether or not the attachment plug cap is inserted.
(a) 15A
(b) 20A
(c) a and b
(d) none of these
- A receptacle must not be installed
within or directly over a bathtub or shower space.
(a) True
(b) False
Article 408 Switchboards and Panelboards
- The purpose or use of panelboard circuits and circuit _____ must be legibly
identified on a circuit directory located on the face or inside of the
doors of a panelboard, and at each switch on a
switchboard.
(a) manufacturers
(b) conductors
(c) feeders
(d) modifications
Article 410 Luminaires, Lampholders,
and Lamps
- Article 410 covers luminaires, lampholders, pendants, and _____ and the wiring and
equipment forming part of such products and lighting installations.
(a) decorative lighting products
(b) lighting accessories for
temporary seasonal and holiday use
(c) portable flexible lighting
products
(d) all of these
- Luminaires subject to physical
damage, using a _____ lamp, installed in playing and spectator seating
areas of indoor sports, mixed-use, or all-purpose facilities must be of
the type that protects the lamp with a glass or plastic lens. Such
luminaires are permitted to have an additional guard.
(a) mercury vapor
(b) metal halide
(c) fluorescent
(d) a or b
- Luminaires containing a metal
halide lamp, other than a thick-glass parabolic reflector lamp (PAR), must
be provided with a containment barrier that encloses the lamp, or the
luminaire must be provided with a physical means that only allows the use
of a _____.
(a) Type “O” lamp
(b) Type PAR lamp
(c) a or b
(d) inert gas
Article 422 Appliances
- A storage-type water heater
having a capacity of _____ gallons or less is considered a continuous
load.
(a) 60
(b) 75
(c) 90
(d) 120
- For permanently-connected
appliances rated over _____ or 1/8 hp, the branch-circuit switch or
circuit breaker is permitted to serve as the disconnecting means where the
switch or circuit breaker is within sight from the appliance or is capable
of being locked in the open position with a permanently installed locking
provision.
(a) 200 VA
(b) 300 VA
(c) 400 VA
(d) 500 VA
Article 424 Fixed Electric
Space-Heating Equipment
- Fixed electric space-heating
equipment is considered a(n) _____ load.
(a) noncontinuous
(b) intermittent
(c) continuous
(d) none of these
Chapter 5
Special Occupancies
Article 500 Hazardous (Classified) Locations,
Classes I, II and III, Divisions 1 and 2
- For listed explosionproof
equipment, factory threaded entries must be made up with at least _____
threads fully engaged.
(a) 5
(b) 4 ½
(c) 6
(d) no minimum
Article 501 Class I
Locations
- A conduit
seal fitting must be installed in each conduit that passes from a Class I,
Division 2 location into an unclassified location. Conduit boundary seals
are not required to be _____, but must be identified for the purpose of minimizing
the passage of gases under normal operating conditions.
(a) listed
(b) installed
(c) explosionproof
(d) accessible
Article 511 Commercial Garages, Repair, and
Storage
- Any pit or depression below a
garage floor level of a lubrication or service room where Class I liquids
are not transferred is considered to be a Class I, Division _____ location
up to floor level and extending 18 in. above floor level and 3 ft
horizontally.
(a) 1
(b) 2
(c) 3
(d) not classified
- Where CNG (compressed natural gas)
vehicles are repaired or stored, the area within _____ in. of the ceiling
is classified as Class I, Division 2, except where ventilation of at least
1 cubic ft per minute per sq ft (cfm/sq ft) of
ceiling area is taken from a point within 18 in. of the highest point in
the ceiling of major repair garages.
(a) 6
(b) 12
(c) 18
(d) 24
Article 514 Motor Fuel Dispensing Facilities
Article 514
applies to _____ and fleet vehicle motor fuel dispensing facilities.
(a) motor
fuel dispensing facilites located inside or outside
(b) marine
fuel dispensing facilities
(c) commercial
gas stations for motor vehicles only
(d) both
a and b
Article 517 Health Care Facilities
- Receptacles located within the
rooms, bathrooms, playrooms, activity rooms, and patient care areas of
pediatric wards, rooms or areas must be listed _____.
(a) tamper
resistant
(b) isolated
(c) GFCI protected
(d) specification grade
Article 525 Carnivals, Circuses, Fairs, and
Similar Events
- Where multiple services or separately
derived systems or both supply rides, attractions, and other structures of
carnival, circuses, fairs and similar events, all sources of supply that
serve rides, attractions, or other structures separated by less than _____
must be bonded to the same grounding electrode system.
(a) 12 ft
(b) 8 ft
(c) 16 ft
(d) 6 ft
- At carnivals, circuses, and
fairs, GFCI protection is not required for receptacles that only
facilitate the quick disconnecting and reconnecting of electrical
equipment and are of the locking type.
(a) True
(b) False
Article 547 Agricultural Buildings
- All 15 and 20A, 125V, 1Ø
general-purpose receptacles installed _____ of agricultural buildings must
have ground-fault circuit-interrupter protection for personnel.
(a) in
areas having an equipotential plane
(b) outdoors
(c) in dirt confinement areas for
livestock
(d) any of these
Article 551 Recreational Vehicles and
Recreational Vehicle Parks
- A minimum of 20 percent of all recreational
vehicle sites with electrical supply must each be equipped with a _____ ,125/250V receptacle.
(a) 15A
(b) 20A
(c) 30A
(d) 50A
Article 555 Marinas and Boatyards
Electrical
wiring and equipment at marine craft repair facilities containing flammable or
combustible liquids or gases must comply with the requirements contained in
_____
(a) Article 511
(b) Article 555
(c) Article 513
(d) a
and b
Article 590 Temporary Installations
- Vegetation cannot be used for
support of overhead spans of _____.
(a) branch
circuits
(b) feeders
(c) holiday lighting branch
circuits with proper strain relief
(d) a or b
Chapter 6
Special Equipment
Article 605 Office Furnishings (Wired
Partitions)
Multiwire branch
circuits that supply power to the wired partitions of office furnishings for
_____ must be provided with a means to simultaneously disconnect all ungrounded
conductors where the branch circuit originates.
(a) fixed-type partitions
(b) free-standing type partitions
(c) both
a and b
(d) none
of these
Article 625 Electric Vehicle Charging System
- Electric vehicle supply
equipment that is identified for and intended to be interconnected to a
vehicle, and also serve _____ , must be listed as
suitable for that purpose.
(a) as an optional standby system
(b) as an electric power production
source
(c) to provide bidirectional power
feed
(d) all of these
Article 640 Audio Signal Processing,
Amplification, and Reproduction Equipment
- Audio cables installed exposed
on the surface of ceiling and sidewalls must be supported by the
structural components of the building in such a manner that the cable will
not be damaged by normal building use. Such cables must be supported by
_____ designed and installed so as not to damage the cable.
(a) straps
(b) staples
(c) hangers
(d) any of these
Article 680 Swimming Pools, Fountains, and
Similar Installations
- All wet-niche luminaires
installed in swimming pools must be removable from the water for relamping
or normal maintenance and must be installed in such a manner that
personnel can reach the luminaire for relamping, maintenance, or
inspection while _____.
(a) the pool is drained
(b) the person is on the deck or a
dry location
(c) during construction
(d) all of these
- 15 and 20 amp, 1Ø, 125 volt
receptacles located within _____ of the inside walls of a storable pool
must be protected by a ground-fault circuit interrupter.
(a) 8 ft
(b) 10 ft
(c) 15 ft
(d) 20 ft
Article 695 Fire Pumps
- The _____
for a transformer that supplies fire pumps must carry indefinitely the sum
of the locked-rotor current of the fire pump motor(s)
and the pressure maintenance pump motor(s), and
the full-load current of the associated fire pump accessory equipment when
connected to this power supply.
(a) primary overcurrent protective
device(s)
(b) pump motor conductors
(c) both a and b
(d) none of these
Chapter 7
Special Conditions
Article 700 Emergency Systems
- Overcurrent protection devices for
emergency power systems _____ all supply-side overcurrent protective
devices.
(a) must be selectively coordinated
with
(b) are allowed to be selectively
coordinated with
(c) must be the same amperage as
(d) must be a larger amperage than
Article 701 Legally Required Standby Systems
- Overcurrent protection devices
for legally required power systems _____ all supply side overcurrent
protective devices.
(a) must be selectively coordinated
with
(b) are allowed to be selectively
coordinated with
(c) must be the same amperage as
(d) must be a higher amperage than
Article 702 Optional Standby Systems
- Where a
generator for an optional standby system is installed outdoors and
equipped with a readily accessible disconnecting means located _____ , an additional disconnecting means is not required
where ungrounded conductors serve or pass through the building or
structure.
(a) inside
the building or structure
(b) within
sight of the building or structure
(c) inside
the generator enclosure
(d) a or c
Article 725 Class 1, Class 2, and Class 3
Remote-Control, Signaling and Power-Limited Circuits
- Class 1, 2, and 3 cables
installed _____ on the surface of ceilings and sidewalls must be supported
by the building structure in such a manner that the cable will not be
damaged by normal building use.
(a) exposed
(b) concealed
(c) hidden
(d) a and b
- Listed plenum signaling
raceways are permitted to be installed in other spaces used for
environmental air as described in 300.2