Instructions: www.garyklinka.com
Article 90 Introduction
1. In order for equipment
and materials to receive approval _____.
(a) the equipment and material must be listed by UL
(b) the authority having jurisdiction must decide on approval
(c) the authority having jurisdiction can never approve non-listed items
(d) the local electrical distributor must decide on approval
Chapter 1 General
Article 110 Requirements for Electrical Installations
2. Unused cable or raceway
opening in electrical equipment shall be_____.
(a) filled with cable clamps or connectors only
(b) taped over with electrical tape
(c) repaired by weldng or brazing in a metal slug
(d) effectively closed by fittings that provide protection equivalent to the
wall of the equipment
3. For mounting electrical
equipment on a masonry wall, it is acceptable to drill a hole in the masonry
and drive a wooden plug into the hole, then use sheet rock screws drilled into
the wooden plug.
(a) True (b) False
4. The termination
provisions of equipment for circuits rated 100 amperes or less or marked for 14
AWG through 1 AWG conductors shall be used only for conductors rated _____ or
conductors with higher temperature ratings provided their ampacity is
determined based on the ____ ampacity of the conductor size used unless the
equipment is listed or identified for use with higher temperature rated
conductors.
(a) 60 degrees C (b) 75 degrees C (c) 30 degrees C (d) 90
degrees C
5. The termination provisions of equipment for circuits rated over 100
amperes or marked for conductors larger than 1 AWG, shall be used only for
conductors rated _____ or conductors with higher temperature ratings provided
their ampacity is determined based on the ____ ampacity of the conductor size
used unless the equipment is listed or identified for use with higher
temperature rated conductors.
(a) 60 degrees C (b) 75 degrees C (c) 30 degrees C (d) 90 degrees C
6. The identification of
the high leg (wild leg) of a 3 phase 4 wire delta connected system shall be
done using _____.
(a) red in color or colored red by an effective means
(b) orange in color or colored orange by an effective means
(c) permanent lettering on the conductor installed by the manufacturer of the
wire
(d) this is no longer required
7. Identification of the
high leg of a 3 phase 4 wire delta connected system shall be required _____.
(a) at the service disconnect only
(b) at each point on the system where a connection is made if the equipment
grounding conductor is also present
(c) at each point on the system where a connection is made if the grounding
electrode conductor is also present
(d) at each point on the system where a connection is made if the grounded
conductor is also present
8. Switchboards, panelboards industrial control panels, and motor control
centers that are in other than dwelling occupancies and are likely to require
examination, adjustment, servicing, or maintenance while _____ shall be field
marked to warn qualified persons of potential electric arc flash hazards.
(a) being installed (b) energized
(c) de-energized (d) in fault condition
9. The manufacturer's name,
trademark, or other descriptive marking shall be placed on all electric
equipment. Where required by the Code, markings such as voltage, current,
wattage, or other ratings shall be provided with sufficient durability to
withstand _____.
(a) the voltages encountered (b) painting and other
finishes applied
(c) the environment involved. (d) Lack of planning by the installer
10. All installed
disconnecting means shall be legibly marked to indicate their purpose unless
they are located and arranged so _____.
(a) that they can be locked out and tagged
(b) they are not readily accessible
(c) their purpose is evident
(d) that they operate at less than 300 volts to ground
11. For equipment rated
1,200A or more and having a width of over 6 ft, at least one entrance,
measuring not less than 24 in. wide and 61/2 ft high, shall be provided at each
end of the working space. Where the entrance to the working
space has a door, the door_____.
(a) shall open either in or out with simple pressure and shall not have any
lock
(b) shall open out and be equipped with panic hardware or other devices so the
door can open under simple pressure without the use of hands.
(c) shall be removed
(d) shall be equipped with an electronic opener
12. Illumination shall be
provided for all working spaces about service equipment, switchboards,
panelboards, and motor control centers _____.
(a) over 600 volts (b) located indoors
(c) rated 1200 amps or more (d) using automatic means of control
Chapter 2 Wiring and Protection
Article
200 Use and Identification of Grounded Conductors
13. The means of
identification of _____ to which a grounded conductor is to be connected shall
be substantially white in color.
(a) wirenuts (b) circuit
breakers (c) terminals (d) ground rods
14. The screw shell of a
luminaire or lampholder shall be connected to the
_____
(a) grounded (neutral) conductor (b) ungrounded conductor
(c) equipment grounding conductor (d) forming shell terminal
Article 210 Branch Circuits
15. The rating of a branch
circuit is determined by the rating of the_____.
(a) ampacity of the largest device connected to the
circuit
(b) average of the ampacity of all devices
(c) branch-circuit overcurrent protection device
(d) ampacity of the branch circuit conductors according to table 310.16
16. Two or more ____, 1Ø,
120V small-appliance branch circuits shall be provided to supply power for 15A
or 20A receptacle outlets in the dwelling unit kitchen, dining room, breakfast
room, pantry, or similar dining areas.
(a) 15 amp (b) 20 amp (c) 30 amp (d) either 15 or 20 amp
17. Receptacle outlets
installed for a specific appliance, such as a clothes washer, dryer, range, or
refrigerator, shall be within _____ of the intended location of the appliance.
(a) sight (b) 6 feet
(c) 3 feet (d) readily accessible, no maximum distance
18. In a dwelling unit, the
minimum required receptacle outlets shall be in addition to receptacle outlets
that are _____.
(a) part of a luminaire or appliance (b) located
within cabinets or cupboards
(c) more than 51/2 ft above the floor (d) all of these
19. A receptacle connected
to the small-appliance branch circuit can be used to supply an electric clock.
(a) True (b) False
20. A receptacle connected
to the small-appliance circuit can supply gas-fired ranges, ovens, or
counter-mounted cooking units.
(a) True (b) False
21. Receptacles installed
in a kitchen to serve countertop surfaces shall be supplied by not fewer than
_____small-appliance branch circuits.
(a) one (b) two (c) three (d) no minimum
22. Lighting outlets can be
controlled by occupancy sensors equipped with a _____ that will allow the
sensor to function as a wall switch.
(a) manual override (b) photo cell
(c) GFCI device (d) Selenium Controlled Rectifier (SCR)
Article 215 Feeders
23. On a _____system where the midpoint of one phase winding
is grounded, the conductor having the higher voltage-to-ground shall be identified
by an outer finish that is orange in color, or by other effective means. Such
identification shall be placed at each point where a connection is made if the
grounded conductor is also present.
(a) single phase 3 wire (b) 3 phase, 4-wire delta-connected
(c) 3 phase 4 wire wye-connected (d) 3 phase 3 wire delta-connected
To obtain your Continuing Education Credits
follow the below instructions.
Send by mail
----------------------------Educational Course Attendance Verification Form ------------------------
Attendee’s Name Date
Address
Credential Number Phone#
Course Title and Name Testelect 24
List the name of each credential held by attendee
Credited Hours 2 hrs
Email address Fax#
--------------------------------------------------------------------------------------------------------
To be completed by Gary Klinka www.garyklinka.com My credential link #70172
Course Password Course ID# 6800
Attendee passed the course with a greater than 70% score on Date
Instructor Signature