Instructions: back to home page
- Print
these pages.
- Circle
the correct answers.
- Page
down to the last page for the verification forms and mailing instructions.
Grounding
and Bonding 60 questions 2hour CEU correspondence course based on the 2005 NEC.
- A (n) _____ is an unintentional, electrically conducting
connection between an ungrounded conductor of an electrical circuit and
the normally non–current-carrying conductors, metallic enclosures,
metallic raceways, metallic equipment, or earth.
- grounded
conductor
- ground
fault
- equipment
ground
- bonding
jumper
250.2
- For grounded systems, noncurrent-carrying conductive
materials enclosing electrical conductors or equipment, or forming part of
such equipment, shall be connected to earth so as to limit the
voltage-to-ground on these materials.
A.
True
B. False
250.4(A)(2)
- For ungrounded systems, non–current-carrying conductive
materials enclosing electrical conductors or equipment, or forming part of
such equipment, shall be connected together and to the supply system
grounded equipment in a manner that creates a permanent, low-impedance
path for ground-fault current that is capable of carrying _____.
- the
maximum branch circuit current
- at
least twice the maximum ground fault current
- the
maximum fault current likely to be imposed on it
- the
equivalent to the main service rating
250.4(B)(2)
- Grounding electrode conductor fittings shall be protected
from physical damage by being enclosed in _____ where there may be a
possibility of physical damage.
- metal
- wood
- the
equivalent of a or b
- none
of these
250.1
- Where the service-entrance phase conductors are installed
in parallel, the size of the grounded conductor in each raceway shall be
based on the size of the ungrounded service-entrance conductor in the
raceway, but not smaller than _____.
- 1/0
AWG
- 2/0
AWG
- 3/0
AWG
- 4/0
AWG
250.24(C)(2) and 310.4
- An unspliced _____ that is sized based on the derived phase
conductors shall be used to connect the equipment grounding conductors of
a separately derived system to the grounded conductor.
- system
bonding jumper
- equipment
grounding conductor
- grounded
conductor
- grounding
electrode conductor
250.30(A)(1)
- Each tap conductor to a common grounding electrode
conductor for multiple separately derived systems shall be sized in
accordance with _____ based on the derived phase conductors of the separately
derived system it serves.
- 250.122
- 250.66
- 310.15
- 250.118
250.30(A)(4)(b)
- A grounding electrode at a separate building or structure
is required where one multiwire branch circuit serves the building or
structure.
A. True
B. False
250.32(A) Ex
- High-impedance grounded neutral systems shall be permitted
for three-phase ac systems of 480 volts to 1000 volts where the conditions
of maintenance and supervision ensure that only qualified persons service
the installation and _____.
- continuity
of power is required
- ground
detectors are installed on the system
- line-to-neutral
loads are not served
- all
of these
250.36
- An electrode encased by at least 2 in. of concrete, located
within and near the bottom of a concrete foundation or footing that is in direct
contact with the earth, is allowed as a grounding electrode when it
consists of _____.
- at
least 20 ft of ˝ in. or larger steel reinforcing bars or rods
- at
least 20 ft of bare copper conductor of 4 AWG or larger
- a or
b
- none
of these
250.52(A)(3)
- _____ shall not be used as grounding electrodes.
- Metal
underground gas piping systems
- Aluminum
electrodes
- Metal
well casings
- a
and b
250.52(B)(1) and (2)
- Plate electrodes shall be installed not less than _____
below the surface of the earth.
- 8 ft
- 24
in.
- 30
in.
- 18
in.
250.53(H)
- When multiple ground rods are used for a grounding
electrode, they shall be separated not less than _____ apart.
- 6 ft
- 8 ft
- 20
ft
- 12
ft
250.56
- Grounding electrode conductors _____ and larger that are not
subject to physical damage can be run exposed along the surface, if
securely fastened to the construction.
- 6
AWG
- 8
AWG
- 10
AWG
- 4
AWG
250.64(B)
- The connection of the grounding electrode conductor to a
buried grounding electrode (driven ground rod) shall be made with a listed
terminal device that is accessible.
A.
True
B.
False
250.68(A) Ex 1
- Metal enclosures and raceways for other than service
conductors shall be grounded except as permitted by 250.112(I).
A. True
B
False
250.86
- Bonding jumpers shall be used around _____ knockouts that
are punched or otherwise formed so as to impair the electrical connection
to ground. Standard locknuts or bushings shall not be the sole means for
this bonding.
- concentric
- eccentric
- field-punched
- a or
b
250.92(B)
- Equipment bonding jumpers shall be of copper or other
corrosion-resistant material. A bonding jumper shall be a _____ or similar
suitable conductor.
- conductor
- bus
- screw
- any
of these
250.102(A)
- The general rule for equipment bonding jumpers installed on
the outside of a raceway or enclosure is that they are not permitted to be
longer than 6 ft, but an equipment bonding jumper can be longer than 6 ft
at outside pole locations for the purpose of bonding or grounding isolated
sections of metal raceways or elbows installed in exposed risers of metal
conduit or other metal raceways.
A.
True
B.
False
250.102(E) Ex
- Metal raceways, enclosures, frames, and other
noncurrent-carrying metal parts of electric equipment installed on a
building equipped with a lightning protection system may require spacing
from the lightning protection conductors, typically 6 ft through air or
___ through dense materials, such as concrete, brick, wood, etc.
- 2 ft
- 3 ft
- 4 ft
- 6 ft
250.106 FPNs
- Liquidtight flexible metal conduit (LFMC) up to trade size
˝ can be used as the equipment grounding conductor if the length in any
ground return path does not exceed 6 ft and the circuit conductors
contained in the conduit are protected by overcurrent devices rated at
_____ or less when the conduit is not installed for flexibility after
installation.
- 15A
- 20A
- 30A
- 60A
250.118(6)(b)
- When ungrounded conductors are increased in size, the
equipment grounding conductor is not required to be increased because it is
not a current-carrying conductor.
A. True
B.
False
250.122(B)
- The grounded circuit conductor is permitted to ground
noncurrent-carrying metal parts of equipment, raceways, and other
enclosures at the supply side or within the enclosure of the ac service
disconnecting means.
A.
True
B.
False
250.142(A)
- A grounded circuit conductor shall not be used for
grounding noncurrent-carrying metal parts of equipment on the load side of
_____.
- the
service disconnecting means
- the separately
derived system disconnecting means
- overcurrent
protection devices for separately derived systems not having a main
disconnecting means
- all
of these
250.142(B)
- The grounding conductor for secondary circuits of
instrument transformers and for instrument cases shall not be smaller than
_____ AWG copper.
- 18
- 16
- 14
- 12
250.178
Current Flow
- When electrical current is given multiple conductive paths
on which to flow, current will only take the path of least resistance.
A. True
B. False
Reference: In parallel paths, current divides and flows through
each individual parallel path in accordance with Kirchoff's current law. So,
when given multiple conductive paths on which to flow, current will take all of
the available paths. Yes, it’s true that more current will flow through the
lower resistive path, as compared to a higher resistive path in a parallel
circuit, but that’s not the question.
Current Flow
- It is important to ground metal parts to a suitable grounding
electrode, so that in the event of a ground fault, dangerous ground-fault
current will be shunted into the earth, away from persons; thereby
protecting them against electric shock.
A. True
B. False
Reference: A person touching an energized metal pole, which is
only grounded, will experience between 90 and 120 mA of current flow
through the body, which is more than sufficient to cause electrocution*. *The
destruction of life by means of electric current, IEEE/ANSI, Std 100. Remember:
In parallel circuits, current divides and flows through each individual
parallel path. Current Through Person I = E/R I =
90V*/1,000 ohms** I = 0.090A or 90 mA *IEEE 142, Grounding Industrial and
Commercial Installations. ** IEEE 80, IEEE Guide for Safety in AC
Substations. Current Through Earth I = E/R I = 120V/25 ohms I = 4.8A, not
enough to trip the circuit breaker Voltage on metal parts can never be reduced
or removed by grounding the metal parts to the earth. The only way to
make an installation safe from a ground fault is to bond the
electrical equipment to an effective ground-fault current path so that
the fault current will be more than sufficient to quickly open the circuit
protection device and clear the ground fault [250.2 and 250.4(A)(3)].
Current Flow
- The grounding conductor for a supplementary grounding
electrode (for example, a ground rod for a machine tool) must have the
capacity to conduct safely any fault current likely to be imposed on it.
This is accomplished by sizing the conductor in accordance with Table
250.66 or Table 250.122, depending on the conditions.
A. True
B. False
Reference: A supplementary electrode is not required to be sized
in accordance with the NEC [250.54]. During a ground fault, the amount
of current flowing through the grounding conductor into the earth, to
the power supply, is dependent on the circuit voltage and the earth’s
resistance. Assuming a circuit voltage of 120 and a ground rod resistance of 25
ohms, the current flowing through the grounding conductor into the
earth, to the power supply, will be only 4.8A, not enough to trip the circuit
breaker. I = E/R I = 120V/25 ohms I = 4.8A Because of the earth’s high
resistance, it cannot be used as an effective ground-fault current path
[250.4(A)(5)]; therefore, the grounding conductor
for a supplementary electrode is not sized in accordance with the NEC [250.54].
Clear a Fault
- Electrical equipment must be grounded so that
sufficient fault current will flow through the circuit protection device
to quickly open and clear the ground fault. For example, a 20A
circuit breaker will trip and de-energize a 120V ground fault to a
metal pole that is grounded to a 25 ohm ground rod.
A. True
B. False
Reference: A ground fault that relies on the earth as the
fault return path to the source is not capable of carrying sufficient current
to clear the ground fault [250.4(A)(5)]. Result… dangerous voltage
between the metal parts and the earth exists. Assuming a circuit voltage of 120
and a ground rod resistance of 25 ohms, the current flowing through the grounding
conductor into the earth, to the power supply, will be only 4.8A, not
enough to trip the circuit breaker. I = E/R I = 120V/25 ohms I = 4.8A Current Through Person I = E/R I = 90V*/1,000 ohms** I = 0.090A or
90 mA *IEEE 142, Grounding Industrial and Commercial Installations. **
IEEE 80, IEEE Guide for Safety in AC Substations. If the metal pole were
bonded to an effective ground-fault current path, the
ground-fault current would be sufficient to quickly open the 20A circuit
protection device [250.2 and 250.4(A)(3)]. Result…
dangerous voltage on metal parts will be removed. I = E/ZT I =
120V/0.405 ohms* I = 296A *Effective ground-fault current path:
Service: 100 ft
of 3/0 AWG Copper Service Z = 0.0766 ohms per 1,000 ft x 0.20 (Chapter 9 Table
8) Service Z = 0.015 ohms
Branch Circuit:
100 ft of 12 AWG Copper Branch Z = 1.93 ohms per 1,000 ft x 0.20 (Chapter 9
Table 8) Branch Z = 0.39 ohms
Electrical Equipment
- Electrical equipment must be grounded to ensure that
dangerous voltage on metal parts resulting from a ground fault can
be reduced to a safe value.
A. True
B. False
Reference: Grounding metal parts to the earth does not
reduce voltage on metal parts resulting from a ground fault because the
earth cannot serve as an effective ground-fault current path [250.5(A)(5)]. Assuming a circuit voltage of 120 and a ground
rod resistance of 25 ohms, the current flowing through the grounding
conductor into the earth, to the power supply, will be only 4.8A, not
enough to trip the circuit breaker. I = E/R I = 120V/25 ohms I = 4.8A Current Through Person I = E/R I = 90V*/1,000 ohms** I = 0.090A or
90 mA *IEEE 142, Grounding Industrial and Commercial Installations. **
IEEE 80, IEEE Guide for Safety in AC Substations. The only way to make
this installation safe from a ground fault is to bond the
electrical equipment to an effective ground-fault current path so that
the fault current will be more than sufficient to quickly open the circuit
protection device; thereby clearing the ground fault and removing
dangerous touch voltage [250.2 and 250.4(A)(3)].
Electrical Equipment
- Metal traffic signal poles and handhole covers must be grounded
to a suitable grounding electrode to ensure that dangerous voltage
on metal parts resulting from a ground fault can be reduced to a
safe value.
A. True
B. False
Reference: Grounding metal parts to the earth does not
reduce voltage on metal parts resulting from a ground fault because the
earth cannot serve as an effective ground-fault current path [250.5(A)(5)]. The only way to make this installation safe from
a ground fault is to bond the metal traffic signal poles and
handhole covers to an effective ground-fault current path so that the
fault current will be more than sufficient to quickly open the circuit protection
device; thereby clearing the ground fault and removing dangerous touch
voltage [250.2 and 250.4(A)(3)].
Electrical Equipment
- Grounding of metal manhole covers to a suitable grounding
electrode ensures that dangerous voltage on metal parts resulting from
a ground fault can be reduced to a safe value.
A. True
B. False
Reference: Grounding metal parts to the earth does not
reduce voltage on metal parts resulting from a ground fault because the
earth cannot serve as an effective ground-fault current path [250.5(A)(5)]. The only way to make this installation safe from a ground
fault is to isolate the manhole cover from energized parts or to bond
the metal parts to an effective ground-fault current path so that the
fault current will be more than sufficient to quickly open the circuit
protection device; thereby clearing the ground fault and removing
dangerous touch voltage [250.2 and 250.4(A)(3)].
Service Equipment
- Service equipment must be grounded to a grounding
electrode to ensure that dangerous voltage on metal parts, caused by a
ground fault, can be removed or be reduced to a safe value.
A. True
B. False
Reference: Grounding metal parts to the earth does not
removing or reduce voltage on metal parts resulting from a ground fault
because the earth cannot serve as an effective ground-fault current path
[250.5(A)(5)]. The only way to make this installation
safe from a ground fault is to bond service equipment to an effective
ground-fault current path so that the fault current will be more than
sufficient to quickly open the circuit protection device; thereby clearing the ground
fault and removing dangerous touch voltage [250.2, 250.4(A)(3), and
250.24(C)].
Service Equipment
- Service equipment is grounded to a grounding electrode
to ensure that metal parts, subject to a ground fault, remain at the same
potential as the earth.
A. True
B. False
Reference: Grounding metal parts to the earth serves no
part in reducing the difference of potential between metal parts and the earth from
a ground fault. The only way to make this installation safe is to bond
service equipment to an effective ground-fault current path so that
the ground fault current will be more than sufficient to quickly open
the circuit protection device; thereby clearing the ground fault and
removing dangerous touch voltage [250.2, 250.4(A)(3), and 250.24(C)].
Service Equipment
- Grounding of service equipment to a grounding
electrode is necessary to stabilize the system voltage.
A. True
B. False
Reference: The earth serves no part in stabilizing the system
voltage. System voltage is stabilized by the grounding of the utility secondary
winding [250.4(A)(1)].
Service Equipment
- The grounding of service equipment ensures that all metal parts
of equipment that personnel can come into contact with, are always at or
near zero (0) volts with respect to ground (earth).
A. True
B. False
Reference: The earth serves no purpose in establishing or
maintaining a zero difference of potential between metal parts of electrical
equipment and the earth during a ground fault.
Separately Derived System
- The metal parts of separately derived systems are grounded
to ensure that the voltage, as measured between the metal parts of the
electrical installation and the earth remains at the same potential during
a ground fault.
A. True
B. False
Reference: The earth serves no purpose in establishing or
maintaining a zero difference of potential between metal parts of electrical
equipment and the earth.
Separately Derived System